Publication 1760-UM002B-EN-P - March 2005
4-142 Wiring with Pico GFX-70
Variable Setpoint Values
Behavior of the setpoint value when variable values are used.
Variable values can be used.
Variable values must be transferred using operands.
With the time base “s” the value is accepted as a “value in ms”.
The last position is rounded up to a zero or five.
With the time base “M:S” the value is accepted as a “value in s”.
With the time base “H:M:” the value is accepted as a “value in M
(minutes)”.
Example:
Time base “s”
The operand has the value 9504.
The time value is 9.50s.
The Operand value is 45507.
The time value is 45.510s.
Time base "M:S"
The operand has the value 5999.
The time value is 99 min, 59s. This is the maximum value.
Time base "H:M"
The operand has the value 5999.
The time value is 99 hours, 59 min.
Displaying the Parameter Set in the PARAMETERS Menu
+ Access enabled
- Access disabled
Contacts
T 01Q1 to T 32Q1
Coils
T 01EN to T 32EN: trigger coil;
T 01RE to T 32RE: reset coil;
T 01ST to T 32ST: stop coil.
IMPORTANT
The delay times are the same as described for the constants.