Rockwell-automation 1760-xxxx Pico GFX-70 Controllers User Manual Manual do Utilizador Página 183

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 400
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 182
Publication 1760-UM002B-EN-P - March 2005
Wiring with Pico GFX-70 4-73
10. actual value equal to zero
11. out of value range
Range A:
The counter has the value zero.
The contacts C..ZE (actual value equal to zero) and C..FB (lower set
point value undershot) are active.
The counter receives counter values and increases the actual value.
C..ZE drops out as well as C..FB and also when the lower set point
value is reached.
Range B:
The counter counts upwards and reaches the upper set point value.
The “upper set point value reached” contact C..OF becomes active.
Range C:
The coil C..SE is briefly actuated and the actual value is set to the
preset actual value. The contacts go to the respective position.
Range D:
The counting direction coil C..D_ is actuated. If counting pulses are
present, downward count is initiated.
If the lower set point value is undershot, the contact C..FB becomes
active.
Range E:
The reset coil C..RE is activated. The actual value is set to zero.
The contact C..ZE is active.
Range F:
The actual value goes outside the value range of the counter.
The contacts become active according to the direction of the values
(positive or negative).
Vista de página 182
1 2 ... 178 179 180 181 182 183 184 185 186 187 188 ... 399 400

Comentários a estes Manuais

Sem comentários