Publication 1760-UM002B-EN-P - March 2005
4-138 Wiring with Pico GFX-70
Markers MD, MW, MB
Analog inputs IA01 to IA04
IA01: terminal I7
IA02: terminal I8
IA03: terminal I11
IA04: terminal I12
Analog output QA01
Actual value
QV> of another function block
Displaying the Parameter Set in the PARAMETERS Menu
+ Access enabled
- Access disabled
Coils
ST01EN, enable coil.
Memory Requirement of the Set Cycle Time Function Block
The set cycle time function block requires 24 bytes of memory plus 4 bytes per
constant on the function block input.
Function of the Set Cycle Time Function Block
The function block is used to define a fixed cycle time.
Actual cycle time is less than the set cycle time:
If the maximum cycle time present is less than the set cycle time, the set cycle
time is constant.
Actual cycle time is greater than the set cycle time:
If the maximum cycle time present is greater than the set cycle time, the set
cycle time has no effect.
IMPORTANT
The function block must be enabled so that it can work.
Coil ST01EN is active. If coil ST01EN is not active, the
entire function block is deactivated and reset.