Publication 1760-UM002B-EN-P - March 2005
4-48 Wiring with Pico GFX-70
• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04
– IA01: terminal I7
– IA02: terminal I8
– IA03: terminal I11
– IA04: terminal I12
• Analog output QA01
• Actual value
… QV> of another function block
Specifying the marker range without offset
If MB, MW or MD markers are specified at both >I1 and >I2 the number of
the markers is the start of comparison range 1 or 2.
Specifying the marker range with offset
If you wish to work with an offset, specify one of the following variables at
function block input
>I1 or >I2:
• Constant,
• Actual value ..QV of a function block,
• Analog input IA..,
• Analog output QA..
The value at the input is taken as the offset to marker MB01.
Displaying the Parameter Set in the PARAMETERS Menu
• + Access enabled
• -: Access disabled
Contacts
BC01E1 to BC32E1: the number of comparison elements exceeds one of the
comparison ranges.
BC01E2 to BC32E2: the two comparison ranges overlap.
BC01E3 to BC32E3: the specified offset of the comparison ranges is outside
of the permissible range.