4-80 Wiring with Pico GFX-70
Figure 4.33 Pico GFX-70 circuit diagram with high-speed counter
Parameter display and parameter set for high-speed counters:
In the parameter display of a counter relay you change set point values and/or
the preset value and enable of the parameter display.
Value Range
The function block operates in the integer range from
-2147483648 to 2147483647.
Behavior when value range is exceeded
The function block sets the switching contact CH..CY to status 1.
The function block retains the value of the last valid operation.
I 05---------------------------[ CH01EN
I 06---------------------------[ CH01RE
I 07---------------------------[ CH01D_
I 08---------------------------[ CH01SE
CH01OF-------------------------[ Q 01
CH01FB-------------------------[ Q 02
CH01ZE-------------------------[ Q 03
CH01CY-------------------------S M 94
CH01 +
>SH
>SL
>SV
QV>
CH01 High-speed counter function block number 01
+ Appears in the parameter display
>SH Upper set point
>SL Lower set point
>SV Defined actual value (Preset)
QV> Actual value in RUN mode
IMPORTANT
Counter CH counts every rising edge on the counter input.
If the value range is exceeded, the switching contact CH
..CY switches to status 1 for one cycle per rising edge
detected.