Publication 1760-UM002B-EN-P - March 2005
4-108 Wiring with Pico GFX-70
Memory Requirement of the 7-Day Time Switch
The 7-day time switch function block requires 68 bytes of memory plus 4 bytes
per channel used.
Function of the 7-Day Time Switch
The switching points are defined according to the parameters entered.
MO to FR: on the weekdays Mo, Tu, We, Th, Fr
ON 10:00, OFF 18:00: on and off switching times for the individual days of
the week.
MO: every Monday
ON 10:00: switch on time
SA: every Saturday
OFF 18:00: switch off time
Switching on working days
Time switch HW01 switches on Monday to Friday between 6:30 and 9:30 and
between 17:00 and 22:30.
HW01 B +
>DY1 MO
>DY2 FR
>ON 17:00
>OFF 22:30
HW01 A +
>DY1 MO
>DY2 FR
>ON 06:30
>OFF 09:30