Rockwell-automation 1760-xxxx Pico GFX-70 Controllers User Manual Manual do Utilizador Página 212

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 400
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 211
Publication 1760-UM002B-EN-P - March 2005
4-102 Wiring with Pico GFX-70
Figure 4.42 Pico GFX-70 circuit diagram with smoothing function block
Parameter Display and Parameter Set for the FT Function Block
Inputs
The function block inputs >I1, >I2 and >KP can have the following operands:
Constants
Markers MD, MW, MB
Analog inputs IA01 to IA04
IA01: terminal I7
IA02: terminal I8
IA03: terminal I11
IA04: terminal I12
Analog output QA01
Actual value
QV> of another function block
Output
The function block output QV> can be assigned the following operands:
Markers MD, MW, MB
Analog output QA01
M 48----------------------------[ FT17EN
FT17 +
>I1
>TG
>KP
QV>
FT17 FT PT1 signal smoothing filter function block, number 17
+ Appears in the parameter display
>I1 Input value
>TG Recovery time
>KP Proportional gain
QV> Output value, smoothed
IMPORTANT
The recovery time T
g
is the time in which the output value
is calculated.
The recovery time T
g
must be set so that it is an integer
multiple of the cycle time or controller scan time T
c
.
Vista de página 211
1 2 ... 207 208 209 210 211 212 213 214 215 216 217 ... 399 400

Comentários a estes Manuais

Sem comentários