Publication 2098-RM003A-EN-P October 2001
Command Reference 2-115
Positive Peak Current Command
Negative Peak Current Command
Bus Voltage
Format: :aa089fddddcc<cr>
Parameter
Code:
0x089
Valid Function
Codes:
0x0 = Read Working Value
Valid Exception
Codes:
0x08 = Invalid Function Code
Data Fields: dddd Peak positive current command, in units of
Amps*128.
Format: :aa08Afddddcc<cr>
Parameter
Code:
0x08A
Valid Function
Codes:
0x0 = Read Working Value
Valid Exception
Codes:
0x08 = Invalid Function Code
Data Fields: dddd Peak negative current command, in units of
Amps*128.
Format: :aa08Bfddddcc<cr>
Parameter
Code:
0x08B
Valid Function
Codes:
0x0 = Read Working Value
Valid Exception
Codes:
0x08 = Invalid Function Code
Data Fields: dddd Bus voltage, after filtering, in units of Volts.