Publication 900-UM004D-EN-E - July 2010
5-8 Communications Data for Modbus
The program end output can be set when the Program Pattern is not set to 0 (OFF).
This cannot be set if the Number of Multi-SP Uses parameter is set to 2.
PRST: Program start can be set when the Program Pattern is not set to 0 (OFF) but the function will be disabled.
P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.
The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the
Control Output 2 ON/OFF Count Alarm turns ON.
Table 5.7
Address Parameter Name Setting (Monitor) Value Function
Group
Four-byte
mode
Two-byte
mode
0E0C 2E06 Control Output 1 Assignment When control output 1 is a linear output:
H'00000000 (0): Not assigned
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
When control output 1 is an ON/OFF output:
H'00000000 (0): Not assigned
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output
H'00000007 (7): Control output ON/OFF count alarm
Advanced
Setting
0E0E Control Output 2 Assignment H'00000000 (0): Not assigned
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output
H'00000007 (7): Control output ON/OFF count alarm
0E14 2E0A Event Input Assignment 1 H'00000000 (0): None
H'00000001 (1): RUN/STOP (Cannot be set if the “Number of
multi-SP uses” is set to 1 or 2.)
H'00000002 (2): Auto/manual switch (Cannot be set if the
“Number of multi-SP uses” is set to 1 or 2.)
H'00000003 (3): Program Start (Cannot be set if the “Number
of multi-SP uses” is set to 1 or 2.)
H'00000004 (4): Direct/reverse operation
H'00000005 (5): None
H'00000006 (6): 100% AT execute/cancel
H'00000007 (7): 40% AT execute/cancel
H'00000008 (8): Setting change enable/disable
H'00000009 (9): Communications writing enable/disable
H'0000000A (10): Alarm latch cancel
0E16 2E0B Event Input Assignment 2 H'00000000...H'0000000A (0...10) (Same settings as the Event Input
Assignment 1))
0E20 2E10 Auxiliary Output 1 Assignment H'00000000 (0): None
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output
H'00000007 (7): Control output ON/OFF count alarm
0E22 2E11 Auxiliary Output 2 Assignment H'00000000…H'00000007 (0…7) (Same settings as the Auxiliary
Output 1assignments)
0E24 2E12 Auxiliary Output 3 Assignment H'00000000…H'00000007 (0…7) (Same settings as the Auxiliary
Output 1assignments)