Publication 900-UM004D-EN-E - July 2010
Modbus Communications Procedure 4-17
Error Occurred
Example Command and Response
The following example shows the command/response for a Stop command.
(In this case, the slave address is H’01.)
Stop command (command code: H’01; related information: 01)
· Address: H’0000 (fixed)
Write data: H’0101 (Run/Stop, Stop command)
Figure 4.17
Table 4.14
Function
code
Error code Name Description
H’86 H’02 Variable address
error
The write variable address is
incorrect.
The variable area number (2-byte
data) is wrong, or the address is
not 0000 or FFFF.
H’03 Variable data
error
The write data is incorrect.
The write data is out of the
setting range.
Command code or related
information is incorrect
H’04 Operation error The Controller cannot write the data
in its present operating status.
The Communications Writing
parameter is set to “OFF”
(disabled). The command is
received regardless of the
Communications Writing
parameter setting (ON/OFF).
Writing was attempted from
setup area 0 to setup area 1.
Writing was attempted to a
protected parameter from
outside the protect level.
AT execution was in progress.
Processing could not be
performed. For details, refer
to Operation Commands and
Precautions on page 4-18
01 06 00 00 01 01 49 9A(CRC-16)
01 06 00 00 01 01 49 9A(CRC-16)
Command:
Response: