Publication 900-UM004D-EN-E - July 2010
Communications Data for Modbus 5-3
Table 5.2
Address Parameter Name Setting (Monitor) Value Function
Group
Four
Byte
Model
Two
Byte
Model
0500 2500 Operation/Adjustment Protect H’00000000 (0): No restrictions in Operation and Adjustment function groups
H’00000001 (1): Move to Adjustment function group is prohibited.
H’00000002 (2): Display and change of only PV and PV/SP parameters is
allowed.
H’00000003 (3): Display of only PV and PV/SP parameters is allowed.
Protect
0502 2501 Initial Setting/Communications
Protect
H’00000000 (0): Move to Initial Setting/Communications Setting function
group is allowed. (Move to Advanced Setting function group is displayed.)
H’00000001 (1): Move to Initial Setting/Communications Setting function
group is allowed. (Move to Advanced Setting function group is not
displayed.)
H’00000002 (2): Move to Initial Setting/Communications Setting function
group is prohibited.
0504 2502 Setup Change Protection H’00000000 (0): OFF (Changing of setup on controller display is allowed.)
H’00000001 (1): ON (Changing of setup on controller display is prohibited.)
0506 2503 PF Key Protect H’00000000 (0): OFF
H’00000001 (1): ON
0508 2504 Move to Protect function group H’FFFFF831…H’0000270F (1999…9999)
050A 2505 Password to Move to Protect
function group
H’FFFFF831…H’0000270F (1999…9999)
(Can only be set. The monitor value is always H’00000000.)
050C 2506 Parameter Mask Enable H’00000000 (0): OFF
H’00000001 (1): ON
0600 2600 Manual Manipulated Variable
(MV)
Standard: H’FFFFFFCE…H’0000041A (5.0…105.0)
Heating and cooling: H’FFFFFBE6…H’0000041A (105.0…105.0)
Manual
function
group
0602 2601 Set Point SP lower limit…SP upper limit Operation
0608 2508 Heater Current 1 Value Monitor H’00000000…H’00000226 (0.0…55.0)
060A 2605 MV Monitor (Heating) Standard: H’FFFFFFCE…H’0000041A (5.0…105.0)
Heating and cooling: H’00000000…H’0000041A (0.0…105.0)
060C 2606 MV Monitor (Cooling) H’00000000…H’0000041A (0.0…105.0)