Publication 900-UM004D-EN-E - July 2010
5-4 Communications Data for Modbus
➊ The alarm function can also be used in Controllers without alarm output terminals. In this case, confirm alarm
occurrences via the status data.
Table 5.3
Address Parameter Name Setting (Monitor) Value Function
Group
Four-byte
mode
Two-byte
mode
0700 2700 Cooling Coefficient H’00000001…H’0000270F (0.01…99.99) Adjustment
0708 2704 Dead Band H’FFFFF831…H’0000270F
(−199.9…999.9 for TC/Pt multi-input models)
(−19.99…99.99 for Analog input models)
070A 2705 Manual Reset Value H’00000000…H’000003E8 (0.0…100.0)
070C 2706 Hysteresis (Heating) H’00000001…H’0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)
070E 2707 Hysteresis (Cooling) H’00000001…H’0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)
0710 2708 Control Period (Heat) H’00000000 (0): 0.5
H’00000001…H’00000063 (1…99)
Initial Setting
0712 2709 Control Period (Cool) H’00000000 (0): 0.5
H’00000001…H’00000063 (1…99)
0718 270C SP Ramp Time Unit H’00000000 (0): EU/second
H’00000001 (1): EU/minute
H’00000001 (2): EU/hour
Advanced
Setting
071A 270D SP Ramp Set Value H’00000000 (0): OFF
H’00000001…H’0000270F (1…9999)
Adjustment
071E 270F MV at Stop Standard: FFFFFFCE…H’0000041A (−5.0…105.0)
Heating and cooling: H’FFFFFBE6…H’0000041A
(−105.0…105.0)
0722 2711 MV at PV Error Standard: H’FFFFFFCE…H’0000041A (−5.0…105.0)
Heating and cooling: H’FFFFFBE6to H’0000041A
(−105.0…105.0)
0726 2713 MV Change Rate Parameter H’00000000…H’000003E8 (0.0…100.0)
072C 2716 Lower-Limit Temperature Input Shift
Value
H’FFFFF831…H’0000270F (−199.9…999.9)
0730 2718 Upper-Limit Temperature Input Shift
Value
H’FFFFF831…H’0000270F (−199.9…999.9)
0734 271A Heater Current 1 Value Monitor H’00000000…H’00000226 (0.0…55.0) Operating
0736 271B Heater Burnout Detection 1 H’00000000…H’000001F4 (0.0…50.0) Adjustment
0738 271C Leakage Current Value 1 Monitor H’0000000…H’00000226 (0.0…55.0) Operating
073A 271D HS Alarm 1 H’00000000…H’000001F4 (0.0…50.0) Adjustment
0746 2723 Temperature Input Shift Value H’FFFFF831…H’0000270F (−199.9…999.9)
0748 2724 Heater Current Value 2 Monitor H’00000000…H’00000226 (0.0…55.0) Operating
074A 2725 Heater Burnout 2 Detection H’00000000…H’000001F4 (0.0…50.0) Adjustment
074C 2726 Leakage Current Value 2 Monitor H’00000000…H’00000226 (0.0…55.0) Operating
074E 2727 HS Alarm 2 H’00000000…H’000001F4 (0.0…50.0) Adjustment