5-16 Communications Data for Modbus
When the control output ON time is less than 190 ms, the bit is set to “1” and the heater current is held at the last current value.
“Spare” bits are always OFF.
When read in setup area 1, the status of the bits will be as follows: Alarm outputs: Cleared
Overcurrent: Last value held HB error: Last value held
Input error: Last value held HB and HS outputs: Cleared
Program end output: Cleared Current hold: Last value held
Display range exceeded: Last value held Heating and cooling outputs: Cleared
NA for 900-TC8 , 900-TC16, and 900-TC32
Table 5.11 Status Details
Bit Position Status Bit Description
01
Status
(lower word)
0 Heater Overcurrent (CT1) Not generated Generated
1 Heater Current Hold (CT1) Update Hold
2 A/D Converter Error Not generated Generated
3 HS Alarm Output (CT1) OFF ON
4Spare OFF
5 Display Range Exceeded Not generated Generated
6 Input Error Not generated Generated
7Spare OFF
8 Control Output (Heating) OFF ON
9 Control Output (Cooling) OFF ON
10 HB (Heater Burnout) Alarm Output (CT1) OFF ON
11 HB (Heater Burnout) Alarm Output (CT2) OFF ON
12 Alarm Output 1 OFF ON
13 Alarm Output 2 OFF ON
14 Alarm Output 3 OFF ON
15 Program End Output OFF ON
Status
(upper word)
16 Event Input 1 OFF ON
17 Event Input 2 OFF ON
18 Event Input 3 OFF ON
19 Event Input 4 OFF ON
20 Write Mode Backup mode RAM write mode
21 EEPROM RAM = EEPROM RAM EEPROM
22 Setup Area Setup area 0 Setup area 1
23 AT Execute/Cancel AT canceled AT execution in progress
24 RUN/STOP Run Stop
25 Communications Writing OFF (disabled) ON (enabled)
26 Auto/Manual Switch Automatic mode Manual mode
27 Program Start Reset Start
28 Heater Overcurrent (CT2) Not generated Generated
29 Heater Current Hold (CT2) Update Hold
30 Spare OFF
31 HS Alarm (CT2) OFF ON