Rockwell-automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Manual do Utilizador Página 150

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 164
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 149
Publication 1794-UM065B-EN-E - September 2010
138 Use the 1794-OF8IH Module with the Generic Profile
Channel Analog Fault Mode Selection
Analog Fault Mode Decimal Value Bits
98
10
Min Scale 0 0 0
Max Scale 1 0 0
Hold Last State 2 1 0
User Specified Data Value 3 1 1
Fault Latch Enable
Channel Bits
0 [Adapter Name]:[Slot]:C.Data[4].2
1 [Adapter Name]:[Slot]:C.Data[4].10
2 [Adapter Name]:[Slot]:C.Data[5].2
3 [Adapter Name]:[Slot]:C.Data[5].10
4 [Adapter Name]:[Slot]:C.Data[6].2
5 [Adapter Name]:[Slot]:C.Data[6].10
6 [Adapter Name]:[Slot]:C.Data[7].2
7 [Adapter Name]:[Slot]:C.Data[7].10
Latch Mode Bit 0
Unlatched 0
Latched 1
HART Current Ratio
Channel Bits
0 [Adapter Name]:[Slot]:C.Data[4].3
[Adapter Name]:[Slot]:C.Data[4].4
[Adapter Name]:[Slot]:C.Data[4].5
[Adapter Name]:[Slot]:C.Data[4].6
[Adapter Name]:[Slot]:C.Data[4].7
1 [Adapter Name]:[Slot]:C.Data[4].11
[Adapter Name]:[Slot]:C.Data[4].12
[Adapter Name]:[Slot]:C.Data[4].13
[Adapter Name]:[Slot]:C.Data[4].14
[Adapter Name]:[Slot]:C.Data[4].15
Vista de página 149
1 2 ... 145 146 147 148 149 150 151 152 153 154 155 ... 163 164

Comentários a estes Manuais

Sem comentários