Rockwell-automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Manual do Utilizador Página 149

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 164
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 148
Publication 1794-UM065B-EN-E - September 2010
Use the 1794-OF8IH Module with the Generic Profile 137
Analog Fault Mode
4
(2)
0100420mA in Milliamps 2.00 22.00 2000
(2.000 mA)
22000
(22.000 mA)
1.0 µA
7
(2)
0111420mA in UINT 4.00 20.00 0 65535 0.2441 µA
14
(2)
1110420mA in % Full Scale2.00 22.00 -1250
(-12.50%)
11250
(112.50%)
1.6 µA
(1)
All other formats are invalid.
(2)
HART Communications supported with these data formats only.
Channel Data Formats
Format
(1)
Bits Format Name Signal Range User Range Resolution
15 14 13 12
11 10 9 8
7654 LO HI LO HI
3210
Channel Bits
0 [Adapter Name]:[Slot]:C.Data[4].0
[Adapter Name]:[Slot]:C.Data[4].1
1 [Adapter Name]:[Slot]:C.Data[4].8
[Adapter Name]:[Slot]:C.Data[4].9
2 [Adapter Name]:[Slot]:C.Data[5].0
[Adapter Name]:[Slot]:C.Data[5].1
3 [Adapter Name]:[Slot]:C.Data[5].8
[Adapter Name]:[Slot]:C.Data[5].9
4 [Adapter Name]:[Slot]:C.Data[6].0
[Adapter Name]:[Slot]:C.Data[6].1
5 [Adapter Name]:[Slot]:C.Data[6].8
[Adapter Name]:[Slot]:C.Data[6].9
6 [Adapter Name]:[Slot]:C.Data[7].0
[Adapter Name]:[Slot]:C.Data[7].1
7 [Adapter Name]:[Slot]:C.Data[7].8
[Adapter Name]:[Slot]:C.Data[7].9
Vista de página 148
1 2 ... 144 145 146 147 148 149 150 151 152 153 154 ... 163 164

Comentários a estes Manuais

Sem comentários