Publication 1794-UM065B-EN-E - September 2010
FLEX I/O HART Modules Network Messaging 117
• Response Error
In the following table, values 6…10 are communication errors.
• Assembly Access Error
•Chained data
• Request allowed
• Loop status available
New loop status is available in Status of Loops assembly.
•Lock
Value Meaning
0 No error
1 Timeout on HART loop
2 Invalid long frame address
3Locked
4 Request overflow
5 Response not available
6 Parity error
7 Overrun error
8 Framing error
9 Checksum error
10 Rx buffer overflow
11…15 Reserved
Value Meaning
0 Access to assembly is invalid
1 Access not valid; take next assembly
(See next assembly pointer)
Value Meaning
0 No chained data in next assembly
1 Chained data in next assembly
Value Meaning
0 Request not allowed
1 Request allowed