Rockwell-automation 1771-QB Linear Pos. Manual do Utilizador Página 167

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 166
Troubleshooting
Chapter 11
115
Figure 11.2
Troubleshooting
Flowchart
START
A
Consult PLC
Processor
RUN
Indicator?
Assembly and
Installation
Manual
I/O
adapter
ACTIVE
Indicator
?
Check the module's
Indicators.
Module
Fault
?
Block
Transfer DONE
bits off
?
Display status block
on industrial terminal.
Consult PLC
Installation Manual
Check the module
address in block
transfer instructions.
Power
up the I/O
chassis containing the
module. Return the
module for repair if the
fault indicator remains
lit when you restore
power.
NO
YES
OFF
ON
OFF
ON
NO
YES
2
1
3
4
Vista de página 166
1 2 ... 162 163 164 165 166 167 168 169 170 171 172 ... 225 226

Comentários a estes Manuais

Sem comentários