Publication 1203-5.14 – September 1998
B-2 1203-SSS Converter Parameters
4
Comm Flt Action
Fault
Zero Data
Hold Last
Fault Yes No Determines the action the converter should instruct the
SCANport product to take if the converter detects a
communication problem. This parameter is active only if
control I/O is enabled.
Important:
If you change the value of this parameter, the
user application may not be able to control the product after
a fault.
!
ATTENTION:
Risk of severe bodily injury or equipment
damage exists. The
Comm Flt Action
(4) parameter allows
the user to change the default configuration that would allow
the converter and associated drive to continue to operate if
communication is lost. Precautions should be taken to
assure that your settings for these parameters and your
application do not create a hazard of bodily injury or
equipment damage.
5
Reset Adapter
Ready
Enable
Set Defaults
Ready Yes No Enable = Resets the converter.
Set Defaults = Sets all parameters to their default values.
6
Clear DF1 Counts
Ready
Enable
Ready Yes No Ready = No action.
Enable = Clears all DF-1 statistical parameters.
7
DF1 Packets Sent
0 – 65535 0 No No Reports the number of DF-1 packets sent by the converter.
8
DF1 Packets Rcvd
0 – 65535 0 No No Reports the number of DF-1 packets received by the
converter.
9
Undelivered Msgs
0 – 65535 0 No No Reports the total number of DF-1 messages that were sent
but never acknowledged.
10
ENQs Sent
0 – 65535 0 No No Reports the number of ENQ characters sent by the
converter.
11
ENQ Received
0 – 65535 0 No No Reports the number of ENQ characters received by the
converter.
12
NAKs Received
0 – 65535 0 No No Reports the number of NAK characters received by the
converter.
13
NAK Bad Packet
0 – 65535 0 No No Reports the number of NAKs sent by the converter because
of corrupt packets (improper protocol messages) as
determined by the converter.
14
NAK No Memory
0 – 65535 0 No No Reports the number of NAKs sent by the converter because
the converter ran out of memory to buffer the incoming
messages. The converter will run out of memory when the
previous command has not completed and there is no place
to save the new commands.
15
Duplicate Msgs
0 – 65535 0 No No Reports the number of duplicate messages sent by the
converter. This value contains the total number of
consecutive messages received by this device with the
same TNS number.
#Name
Valid Values/
Settings
Default Writable
Reset or
Power Cycle
to Take
Effect
Description
Important:
For information on editing parameters, refer to Chapter 3,
Configuring the 1203-SSS Converter
.