3-60
SA3100 Drive Configuration and Programming
Meter Port 4
UDC Module Meter Port 4 Register Number Register 1014
UDC register number (0 - 2044) to be mapped to meter port 4. Sug. Var. Name: N/A
Units: N/A
Range: N/A
Access: Read/Write
UDC Module Meter Port 4 Bit Number Register 1015
Bit number of the UDC register specified in register 1002 that is to be
mapped to port 4. Enter a value of 100 (bit 00) to 115 (bit 15) as
required. Enter a value of zero if all of the registers bits are to be
displayed.
Sug. Var. Name: N/A
Units: N/A
Range: N/A
Access: Read/Write
UDC Module Meter Port 4 Maximum Value Register 1016
Set this register to the number that will represent +10V. The
maximum allowable value is 32767.
Sug. Var. Name: N/A
Units: N/A
Range: N/A
Access: Read/Write
UDC Module Meter Port 4 Minimum Value Register 1017
Set this register equal to the number that will represent -10V. The
minimum allowable value is -32768.
Sug. Var. Name: N/A
Units: N/A
Range: N/A
Access: Read/Write