C-30
EtherNet/IP Communications Module
Instance Attributes
Services
Attribute
ID
Access
Rule Name Data Type Description
0 Get Full/All Info STRUCT of
BOOL[32]
CONTAINER
1
CONTAINER
CONTAINER
CONTAINER
WORD
WORD
STRING[4]
UINT
UINT
UINT
INT
DWORD
STRING[16]
Descriptor (Refer to pages C-24 to
C-25)
Value
Minimum value
Maximum value
Default value
Pad Word
Pad Word
Units (e.g., amp, Hz)
Multiplier
2
Divisor
2
Base
2
Offset
2
Link (source of the value) (0 = no link)
Always zero (0)
Parameter name
1 Get/Set Value Various Diagnostic item value
1
A CONTAINER is a 32-bit block of data that contains the data type used by a value.
If signed, the value is sign extended. Padding is used in the CONTAINER to ensure
that it is always 32-bits.
2
This value is used in the formulas used to convert the value between display units
and internal units. Refer to Formulas for Converting on page C-25.
Service Code
Implemented for:
Service NameClass Instance
0x0E Yes Yes Get_Attribute_Single
0x10 Yes Yes Set_Attribute_Single