6-18 Communicating with Devices on an EtherNet/IP Link
Mapping addresses
The programming software includes a PLC/SLC mapping tool which allows
you to make an existing controller array tag in the local controller available to
PLC-2, PLC-3, PLC-5, or SLC controllers.
To map addresses:
1. From the Logic menu, select Map PLC/SLC Messages.
2. Specify this information:
For: In this field: Specify: For example:
PLC-3, PLC-5, and
SLC controllers
File Number Type the file number of the data table in the
PLC/SLC controller.
10
Tag Name Type the array tag name the local controller uses to refer
to the PLC/SLC data table address. The tag must be an
integer array (SINT, INT, or DINT) that is large enough for
the message data.
array_1
PLC-2 controllers Tag Name Type the tag name to be the PLC-2 compatibility file. 200
TIP
You can map as many tags as you want to a PLC-3, PLC-5,
or SLC controller. You can map only one tag to a PLC-2
controller.