Rockwell-automation 284D On-Machine ArmorStart Accelerator Toolkit Manual do Utilizador Página 47

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 188
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 46
Publication IASIMP-QS015C-EN-P - August 2011 47
System Layout and Wiring Chapter 2
ArmorStart Device Wiring
Wiring in an industrial control application can be divided into three groups; power, control, and signal.
Follow these recommendations for physical separation between these to reduce the coupling effect:
Minimum spacing between different wire groups in the same tray should be 16 cm (6 in.).
Run wire outside an enclosure conduit or have shielding or armor with equivalent attenuation.
Run different wire groups in separate conduits.
Minimum spacing between conduits containing different groups should be 8 cm (3 in.).
The table provides power, control, ground wire capacity, and tightening torque requirements. The power,
control, ground, and safety monitor terminals accept a maximum of two-wire per terminal.
Power, Control, Safety Monitor Inputs, Ground Wire Size, and Torque Specifications
Terminal Type Wire Size Torque Wire Strip Length
Power and Ground Primary/secondary terminal
1.5...4.0 mm
2
(16...10 AWG)
Primary terminal - 1.2 N•m (10.8 lb•in.)
Secondary terminal - 0.5 N•m (4.5 lb•in.)
9 mm (0.35 in)
Control and Safety Monitor Inputs
1.0...4.0 mm
2
(18...10 AWG)
0.7 N•m (6.2 lb•in.) 9 mm (0.35 in.)
Vista de página 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 187 188

Comentários a estes Manuais

Sem comentários