9-8 Viewing the Adapter’s Web Pages
The Configure E-mail Notification web page contains selections and
data fields for configuring the adapter to automatically send e-mail
messages to desired addresses when selected types of events occur. By
default, this configuration is not protected. After configuration, the
settings can be protected by setting the Parameter 30 - [Web Features]
E-mail Cfg Bit 0 value to “0” (Disabled). To change a protected
configuration, it must first be unprotected by setting the E-mail Cfg Bit 0
value back to “1” (Enabled). For more information, see Chapter 3
,
Setting Web Features Access.
Figure 9.5 Example of Configure E-mail Notification Web Page
To configure e-mail notification
1. Click the desired Host Faults check boxes you want to occur that will
send e-mail notification:
If you only want e-mail notification when specific faults occur,
click this radio button and type the fault numbers in the box.
If you only want e-mail notification when all faults except
specific faults occur, click this radio button and type the fault
numbers in the box.
Configure E-mail Notification Web Page