24 Foundation Fieldbus Linking Device
Publication
1757-IN021E-EN-P - August 2009
Radiated RF immunity
IEC 61000-4-3
1V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
10V/m with 1 kHz sine-wave 80% AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
900 MHz and 1890 MHz
EFT/B immunity
IEC 61000-4-4
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on shielded Fieldbus ports
±2 kV at 5 kHz on Ethernet ports
Surge transient immunity
IEC 61000-4-5
±2 kV line-earth (CM) on shielded Fieldbus
ports
±2 kV line-earth (CM) on shielded Ethernet
ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz on power ports,
shielded Fieldbus ports, and Ethernet ports
Magnetic field immunity
IEC 61000-4-8
30 A/m long duration at 50 Hz
1757-FFLD2, 1757-FFLD4 - Certifications
(1)
Certification
(2)
Value
c-UL-us UL Listed for Class I, Division 2 Group
A,B,C,D Hazardous Locations, certified for
U.S. and Canada. See UL File E194810.
1757-FFLD2, 1757-FFLD4 - Environmental Specifications
Attribute Value