Publication 1757-PM002A-EN-E - June 2006
4-30 Applications
8. Drag and drop the Input Reference to the left of the PIDE block.
9. Double-click the single ? on the Input Reference and select the
Controller Scoped tag, FFLD:0:I.In[0].Value.
This tag is the IN_0 pin from the RSFieldbus Logix Block and the
LD292 AI input.
10. Press <Enter>.
11. Click the FFLD:0:I.In[0].Value pin, then the Source A pin to connect
them.