Rockwell-automation 1757-FFLD Linking Device Configuration Manual Manual do Utilizador Página 114

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 113
Publication 1757-PM002A-EN-E - June 2006
5-8 Troubleshooting
Is There Power on the H1 Network?
No:
a. Connect a power supply to the network.
Is the Power Supply Connected Through a Proper Power Conditioner?
No:
a. Use a proper power conditioner in accordance with the Foundation
Fieldbus Installation Guide.
Power must be applied to the network through a proper power
conditioner. The power supply cannot be directly connected to the H1
network.
Is There Network Power on the Linking Device Network Connector?
No:
Is There Power on the Terminal or Network Connector Block/Power on the
Output on the Power Conditioner?
No:
a. Repair or replace the power conditioner.
Is the Voltage at the Output of the Power Conditioner 11-30 VDC?
No:
a. Repair, replace or adjust the power supply.
Is the RSFieldbus Project Properly Configured?
Don’t know:
a. Refer to Create A New RSFieldbus Project on page 4-14 and
configure a project or use a known good project file to test the
operation of the linking device on the H1 network. If this does not
work, contact Tech Support for assistance in building a proper
project file.
Yes:
a. Remove power from the linking device.
Vista de página 113
1 2 ... 109 110 111 112 113 114 115 116 117 118 119 ... 149 150

Comentários a estes Manuais

Sem comentários