Add the Linking Device
1. Right-click the ethernet module and select New Module.
2. Select the 1757-FFLD/A and click OK.
3. Enter a name and I/P address.
4. Select Disable Keying and click Finish.
Your linking device is added to the project.
Add Your Logix Block
1. Right-click the linking device and select New Module.
2. The Logix Block is your only choice, so click OK.
3. Enter >FFLD Logix< for the name, and select Disable Keying.
The Slot Value must match the value that you set for the Logix Block Slot
parameter on page 4-16. Because the default is 0, you do not need to change
it here.
4. Click Finish.
The Logix Block is added to the project.