4-20 Application Examples
Create a Ladder Program
The final step is to write a ladder program for the SLC processor, including
configuring the 1747-SCNR for slot 3 of the processors chassis. After
downloading the program to your processor, place it into the RUN mode. Your
program should now be able to read data from the 1746-IA16 in word I:3.3
and write to the 1746-OB16 in word O:3.3. The analog input data resides in
words I:3.7 and I:3.8, while the analog output data must be copied to words
O:3.5 and O:3.6.
Note that your ladder program should also contain an unconditional rung with
an OTE instruction addressed to the SCNR scanners RUN/IDLE bit, O:3.0/
10 for this example. When the SLC processor is placed into the RUN mode,
this rung sets the SCNR scanner’s RUN/IDLE bit and places the scanner into
the RUN mode as well. The scanner begins executing the configured
connections when the RUN/IDLE bit is set.