Publication 1746-6.1.2 - July 2000
Wiring the SLC Servo Module
5-7
Wiring the Estop for a One-Axis System
To wire the Estop for a one-axis system connect the following:
• Drive enable
• Estop reset pushbuttons (Res P.B., Res P.B., and Reset)
• Customer Estop String (String In and String Out)
• An Estop string (Figure 5.5) is connected in series and consists
of:
• Axis hardware overtravels
• Remote Estop
• Motor thermal switch
• Transformer thermal switch
• Drive fault
Wiring for Normal Operation
• Wire the Estop inputs for normal operation.
• Bench test your SLC Servo Modules.
• The Estop Reset pushbutton requires a two-pole single-throw
switch.
Maintaining Electrical Continuity
• Maintain electrical continuity on the termination panel between
the String Out and String In terminals to change from an Estop
state to a run state when pressing the Estop Reset pushbutton.
• While in the run state, loss of continuity between String Out and
String In places the SLC Servo Module in an Estop state.
• All motion is inhibited in the Estop state.
Verifying Connections and Operation
• Verify that the Estop wiring is connected correctly.
• Check the operation of devices wired between String Out and
String In.
ATTENTION
!
To avoid personal injury or hardware damage,
develop a fail-safe wiring design for your Estop
string.