Publication 1746-6.1.2 - July 2000
Programming System Variables
9-9
Typical Set Excess FE Limit Move Data Tables
Before executing a Set Excess FE Limit move, set Source B for the
Equal instruction in Figure 9.1 to 512. A Set Excess FE command to 0.1
is initiated if the data tables are:
Using the Set Axis Gain Command
The Set Axis Gain command sets the current axis gain to equal the
specified value. Set Axis Gain parameters for word 5, bit 10 appear in
the table below.
1
s = Slot number for the SLC Servo Module.
The Set Axis Gain command can be issued anytime after the control is
powered up.
The units for the specified gain are position units per minute per one
thousandth of the position unit. If the Set Axis Gain command fails,
the SLC processor is notified with an appropriate error message.
Typical Set Axis Gain Move Data Tables
Before executing a Set Axis Gain move, set Source B for the Equal
instruction in Figure 9.1 to 1024. A Set Axis Gain command to 0.75 is
initiated if the data tables are:
Word 0 1 2 3 4 5
F27:0 0.1
N32:0 0 0 0 0 0 512
Block Command Parameters
Location
1
Format Possible Values Default
Bit Specifications O:s.4 Bits 0000 0000 0000 0000
0
Set Axis Gain O:s.5 Bits
XXXX X1XX
0000 0000
0
Gain O:s.6-O:s.7 Float 0.0 to 10.0
0.0
Word 0 1 2 3 4 5
F27:0 0.75
N32:0 0 0 0 0 0 1024