Rockwell-automation SB3000 Configuration and Programming Manual do Utilizador Página 103

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 122
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 102
Status of Data in the AutoMax Rack After a STOP_ALL Command or STOP_ALL Fault
D-1
A
PPENDIX
D
Status of Data in the AutoMax Rack
After a STOP_ALL Command or
STOP_ALL Fault
AutoMax Processor UDC Module PMI Processor
LOCAL tunable variables retained retained retained
LOCAL variables retained reset to 0 N/A
COMMON memory variables non-volatile are
retained;
others are reset to 0
N/A N/A
I/O variables
(including UDC dual port memory
inputs retained and
updated;
outputs are reset to 0
inputs retained and
updated;
outputs are reset to 0
all I/O is reset to 0
Input values, including:
Feedback registers
UDC/PMI communication status
registers
UDC Error Log info
retained retained N/A
Output values, including:
Command registers
Application registers
ISCR registers
Scan-per-interrupt register
Scans-per-interrupt counter
reset to 0 reset to 0 N/A
Parameter configuration variables N/A retained N/A
UDC test switch information N/A retained N/A
D/A setup configuration N/A retained N/A
Operating system retained retained retained
Vista de página 102
1 2 ... 98 99 100 101 102 103 104 105 106 107 108 ... 121 122

Comentários a estes Manuais

Sem comentários