CE Conformance Requirements
D-3
EN61000-3-2
0.75 kW (1 HP) 240 V 1-phase and 3-phase drives and
0.37 kW (0.5 HP) 240 V 1-phase drives are suitable for
installation on a private low-voltage power network.
Installations on a public low-voltage power network may require
additional harmonic mitigation.
Other drive ratings meet the current harmonic requirements of
EN61000-3-2 without additional external mitigation.