Store and load a project by using a memory card Chapter 1
Change the load image option
1. On the Nonvolatile Memory tab, click Load/Store.
2. From the Load Image list, choose User Initiated.
3. Click <- Store.
Important:
Store is not active if a SD card is locked.
A dialog box asks you to confirm the store operation.
4. To store the project, click Yes.
A dialog box indicates the store operation is in progress.
5. Click OK.
Wait until the OK status indicator on the front of the controller is steady
green. This indicates the store operation is finished.
Clear the project from the controller
If your application allows you to clear a project, follow these steps.
1. With power still applied to the controller, disconnect the battery or other
energy storage module from the controller.
2. Cycle the power to the chassis.
3. Reconnect the battery or other energy storage module to the controller.
For more information, see these publications.
• ControlLogix Energy Storage Modules Installation Instructions
,
publication 1756-IN616.
• ControlLogix System User Manual, publication 1756-UM001.
Rockwell Automation Publication 1756-PM017F-EN-P – October 2014 23