Publication GMLC-5.2 - November 1999
568 Fault Variables
When System_smrt_pwr_pre-charge_fault_1394 = 1,
System_module_fault_status_1394 = 10.
System Smart Power Shunt Timeout Fault 1394
System_smrt_pwr_shunt_timeout_fault_1394 is a logical (Boolean)
variable, with a value of:
1 (True) if the 34 Amperes Root Mean Square (RMS) continuous or
200 Amperes peak rating of the Smart Power system module shunt
resistor is exceeded by 5%, or
0 (False) if not.
When System_smrt_pwr_shunt_timeout_fault_1394 = 1,
System_module_hard_fault_1394 = 1, and Drive_hard_fault_1394 = 1.
Clearing this fault clears Drive_hard_fault_1394.
When System_smrt_pwr_shunt_timeout_fault_1394 = 1,
System_module_fault_status_1394 = 8.
!
ATTENTION:
A hard fault is a serious condition! Be
certain to correct the underlying cause of this fault,
before clearing the fault and reactivating the drive.
!
ATTENTION:
A hard fault is a serious condition! Be
certain to correct the underlying cause of this fault,
before clearing the fault and reactivating the drive.