BĆ11
888 BCD output number greater than 9999
889 Bad bit number in function call
890 Bad option number in function call
891 Invalid GATEWAY transfer call
Note: Check returned status variable of
GATEWAY_CMD_OK@ function; decode status error numbers as follows
(01 through 07 are MODBUS exception codes):
Decimal
01 Illegal function code
02 Illegal starting register
03 Illegal data
04 PC aborted
05 Not assigned
06 PC busy
07 Not assigned
08 Illegal data in response message
09 Response timeout error
20 Dual port address error
21 Gateway card not found or not accessible
22 No available Gateway channel
23 Illegal register number
24 Illegal number of register
25 Illegal command number
26 Illegal command number/register set
27 Illegal register number/number of registers
28 Illegal device address
892 BLOCK_MOVE invalid source parameter
893 BLOCK_MOVE invalid destination parameter
894 BLOCK_MOVE invalid transfer size parameter
895 RESUME without executing ON ERROR statement first
956 UDC tick rates do not match
958 PMI gains out of range
959 UDC Processor error
960 Floating point format conversion error
961 Spurious interrupt detected from Multibus
962 CCLK must be enabled to execute task
963 OS background not completing
964 Flash update not completing in time; check utilization
Corrective action: For error code 757, check real and double integer value
ranges.
1000 SCR fault
1001 MĆcontactor fault
1002 (not used)
1003 Instantaneous overcurrent fault
1004 Synch loss (AC line voltage)
1005 Conduction timeout
1006 Field loss fault
1007 Tach loss fault