4-4 Using BACnet Objects
Table 4.A BACnet Object Descriptions and Supported Drives (Continued)
Object Name Use This Object to…
Compatible PowerFlex Drives
4 4M 40 400
AV3 Output Current (Amps) Read the drive’s output current. ✔✔✔✔
AV4 Output Voltage (VAC) Read the drive’s output voltage. ✔✔✔✔
AV5 Output Power (kW) Read the drive’s output power. — — ✔✔
AV6 Output Energy (kWh) Read/write the drive’s accumulated output energy.
Note: When writing, this object accepts only a value of “0” (zero).
———✔
AV7 DC Bus Voltage (VDC) Read the drive’s DC bus voltage. ✔✔✔✔
AV8 Drive Temp (°C) Read the drive’s temperature. ✔✔✔✔
AV9Reserved — ————
AV10Reserved — ————
AV11 Run Time (Hours) • PowerFlex 4/4M/40: Read the drive’s accumulated run time.
• PowerFlex 400: Read/write the drive’s accumulated run time.
Note: When writing, this object accepts only a value of “0” (zero).
✔✔✔✔
AV12 Fault 1 Read the code for the drive’s most recent fault. ✔✔✔✔
AV13 Fault 2 Read the code for the drive’s second most recent fault. ✔✔✔✔
AV14 Fault 3 Read the code for the drive’s third most recent fault. ✔✔✔✔
AV15 Accel Time 1 (Sec) Read/write the drive’s Accel Time 1 setting. ✔✔✔✔
AV16 Decel Time 1 (Sec) Read/write the drive’s Decel Time 1 setting. ✔✔✔✔
AV17 Mailbox Param Read/write any drive parameter. To read a drive parameter, write the number
for the desired parameter to the Mailbox Param object, and then read the
Mailbox Value object. To write a drive parameter, write the number for the
desired parameter to the Mailbox Param object, and then write the desired
value to the Mailbox Value object.
✔✔✔✔
AV18 Mailbox Value ✔✔✔✔
Binary Input (BI) Objects
BI0 Stop Input Read the state of the Stop Input on the drive’s I/O terminal block. ✔✔✔✔