Step 5: Remove the
Existing Connections and
Option Board(s)
If the optional resolver feedback module, I/O expansion, and 115V AC to
24V DC converter boards are not installed on the control board, continue with
Step 6: Remove the Existing Control Board
on page 13.
Important:Mark all connections and wires before removing to avoid incorrect
wiring during reassembly.
Step 5A: Remove the Resolver Feedback Module
If the optional resolver feedback module is not installed, continue with Step 5B:
Remove the Optional I/O Expansion Board on page 10.
Important:The resolver feedback module can only be used with PowerFlex DC
drives with firmware version 5.002 or higher.
Important:The resolver feedback module consists of an interface board and a
feedback board. For this procedure, both boards of the resolver
feedback module are removed together, as an assembly.
1. Remove the three plug-in I/O terminal blocks from the resolver feedback
module assembly.
2. Remove the four mounting screws for the resolver interface board.
S15
XR
XA
XP3
XRE
XFCD
S21
S4
J1 J2
P1
S1
TB1 TB2
P4
P2 P3
P1
S2
=
Remove four screws
(resolver interface board)
Tightening torque is
0.7 N•m (6.2 lb•in)
Resolver interface board
Resolver feedback board
Plug-in I/O terminal blocks