Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013 169
Detail Drive Configuration and Operation Chapter 1
The Parameter 1000 - SL Node Cnfg Properties dialog box opens.
4. Clear the Sync Now check box.
5. Check the Time Keeper check box.
The master drive is now the time keeper for SynchLink.
6. Click OK.
The SynchLink communication dialog box re-opens.
7. Click OK.
To synchronize the speed references, you must add a time delay to the S-
Curve speed reference of the master.
8. Open the Properties dialog box for Parameter 37 [Spd Ref Bypass].