Rockwell-automation 20-COMM-I Interbus Adapter Manual do Utilizador Página 87

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 86
Troubleshooting 7-3
(1)
Only visible when drive cover is open.
Bus Active (BA) Status Indicator
Status Cause Corrective Actions
Off Bus not active.
Set master to start data transmission.
Solid Green Bus active, exchanging
data.
No action.
Flash Green Bus active, but no data
exchange.
Set master to start data transmission.
Bus Voltage (UL) Status Indicator
(1)
Status Cause Corrective Actions
Off Bus voltage is not OK.
Securely connect the adapter to the drive
using the Internal interface cable
Apply power to the drive.
Solid Green Bus active.
No action.
20COMM-UM007A-EN-P.book Page 3 Tuesday, January 22, 2002 10:52 AM
Vista de página 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 117 118

Comentários a estes Manuais

Sem comentários