Configuring the Interbus Scanner 4-15
PowerFlex 70 Settings to use with Ladder Examples
The following parameters should be configured to use the example
ladder logic program.
PowerFlex 70
RSLogix 500 SST Interbus Scanner Configuration
The SST Interbus scanner is configured by clicking on the I/O
Configuration in RSLogix500. The SST-IBS-SLC has an ID Code of
13635. The following settings are used by the example ladder logic
program, as shown in Figure 4.18
and Figure 4.19.
Parameter Name Value Description
90 Speed Ref A Sel 22 DPI Port 5 (20-COMM-I) provides the
Reference
300 Data In A1 140 Pr. 140 [Accel Time 1]
301 Data In A2 142 Pr. 142 [Decel Time 1]
302 Data In B1 100 Pr. 100 [Jog Speed]
303 Data In B2 155 Pr. 155 [Stop Mode A]
304 Data In C1 101 Pr. 101 [Preset Speed 1]
305 Data In C2 102 Pr. 102 [Preset Speed 2]
306 Data In D1 103 Pr. 103 [Preset Speed 3]
310 Data Out A1 140 Pr. 140 [Accel Time 1]
311 Data Out A2 142 Pr. 142 [Decel Time]
312 Data Out B1 100 Pr. 100 [Jog Speed]
313 Data Out B2 155 Pr. 155 [Stop Mode A]
314 Data Out C1 101 Pr. 101 [Preset Speed 1]
315 Data Out C2 102 Pr. 102 [Preset Speed 2]
316 Data Out D1 103 Pr. 103 [Preset Speed 3]