Configuring the I/O 4-5
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
There are three ways to add the adapter into the I/O configuration:
Drive Add-on Profiles (RSLogix 5000 software, version 16.00 or later)
Classic Profile (RSLogix 5000 software, versions 13.00…15.00)
Generic Profile (RSLogix 5000 software, all versions)
These are described in separate sections below. If your version of RSLogix
5000 software supports drive Add-on Profiles, we recommend that you use
this method.
Using RSLogix 5000 Drive Add-on Profiles, Version 16.00 or Later
When compared to using the RSLogix 5000 Classic Profile (versions
13.00…15.00) or Generic Profile (all versions), the RSLogix 5000 drive
Add-on Profiles provide the following advantages:
Profiles for specific drives that provide descriptive controller tags for
basic control I/O words (Logic Command/Status and Reference/
Feedback) and Datalinks. Additionally, Datalinks automatically take the
name of the drive parameter to which they are assigned. These profiles
virtually eliminate I/O mismatch errors and substantially reduce drive
configuration time.
New Drive tab eliminates the need for a separate drive software
configuration tool.
Drive configuration settings are saved as part of the RSLogix 5000
software, version 16.00 or later, project file (.ACD) and also downloaded
to the controller.
Unicast connection (requires RSLogix 5000 software, version 18.00 or
later, and 20-COMM-E Series B adapter firmware 4.001 or later)
Drive Add-on Profiles can be updated anytime. When a new drive is
used, or to benefit from new updates for Add-on Profiles, you will need
the newest Add-on Profile update. Go to http://www.ab.com/support/
abdrives/webupdate to download the latest RSLogix 5000 drive Add-on
Profile. To determine your drive Add-on Profile version, see
Allen-Bradley Knowledgebase document #65882.
Add the Drive/Adapter to the I/O Configuration
To transmit data between the bridge and the drive, you must add the drive as
a child device to the parent bridge. In this example, RSLogix 5000 software,
version 16.00 is used with drive Add-on Profile version 3.01.
1. In the treeview, right-click on the bridge and choose New Module… to
display the Select Module screen.