Rockwell-automation 20-COMM-E PowerFlex EtherNet/IP Adapter Manual do Utilizador Página 132

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 296
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 131
6-6 Using Explicit Messaging
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
ControlLogix Controller Example Ladder Logic Program to Read a Single Parameter
Using RSLogix 5000 Software, Any Version
A Get Attribute Single message is used to read a single parameter. This read
message example reads the value of parameter 003 - [Output Current] in a
PowerFlex 7-Class drive.
Important:See Table 6.A on page 6-2
for limitations of PowerFlex 7-Class
and PowerFlex 750-Series drives when using DPI Parameter
Object Class code 0x93 or Host DPI Parameter Object Class
code 0x9F for explicit messaging.
Table 6.C Example Controller Tags to Read a Single Parameter
Figure 6.4 Example Ladder Logic to Read a Single Parameter
Operand Controller Tags for Single Read Message Data Type
XIC Execute_Single_Read_Message BOOL
MSG Single_Read_Message MESSAGE
Vista de página 131
1 2 ... 127 128 129 130 131 132 133 134 135 136 137 ... 295 296

Comentários a estes Manuais

Sem comentários