6–4 Application Layer Message Packets
Publication
17706.5.16 - October 1996
DST and SRC
Form the DST and SRC bytes of a reply message by interchanging
the DST and SRC bytes of the corresponding command message:
DST SRC
SRC DST
Command
Reply
Byte Contents Value supplied by Value range
DST
(destination)
receiving message application layer
0 to 376 (octal) for DF1
0 to 376 (octal) for DH
SRC
(source)
sending message data link layer
0
to
376
(octal)
for
DH
0 to 77 (octal) for DH+
0 to 31 (decimal ) for DH485
When sending messages from asynchronous devices, special
consideration must be given to the SRC byte:
When sending a message from an
asynchronous device connected
Set the SRC byte
to the network
= 0 (the module will set the byte to its own
node number)
directly to a 1771KG
10 (octal)
If
you connect to channel 0 of a PLC5/1
1, 5/20, 5/30, 5/40, 5/60 or 5/80 processor and you
send a PLC2
unprotected write, protected write, protected bit write,
or
unprotected bit write,
what
you put into the SRC byte is very important. This determines the compatibility file. This means
that the value of the SRC byte specifies the data table file number that is written to the PLC5
processor
. The source byte will not be overwritten by channel 0. For SLC 500 processors, the
compatibility file is always 9.