10–7Diagnostic Status Information
Publication
17706.5.16 - October 1996
1770KF3 Status Bytes
Bytes Bits Contents Description
1 1 Mode/Status 00 (no modes)
2 2 Type Extender FE
3 3 Extended Interface Type 2C
4 4 Not used 00
5
04
Series/Revision
= 0 release1; = 1 release 2, etc.
57 = 0 series A; = 1 series B, etc.
6 - 16 all Bulletin Number/Name (in ASCII) 1770KF3
17 - 24 all Product Specific Information 00
1771KA2, KA, KC/KD, KE, KF, KG, KGM, 1770KF2 Status
Bytes
Bytes Bits Contents Description
1
0 - 2
Operating status of
PLC processor
For the 1770KF2, this byte is always 0. For other modules:
0 = Program load mode
1 = Test mode
2 = Run mode
3 = (not used)
4 = Remote Program load
5 = Remote test
3 0 = normal communication; 1 = No communication with PLC
processor
4 0 = Normal; 1 = Download or upload mode
5 0 = Normal; 1 = Format error in communication zone of PLC
program
6 - 7 always zero
2 0 - 3 Type of interface module and processor 0 = 1771KC,KD module
1 = 1771KA2 or (1771KA) module
2 = 1771KA4 module
3 = 1771KE,KF or 1770KF2 module
4 = 1771KG module
5 = 1771KGM module
4 - 7 0 = PLC processor
1 = PLC2 processor
2 = PLC2/20 (LP1) Processor
3 = MiniPLC2 processor
5 = PLC2/20 (LP2) processor
6 = PLC2/02, 2/15,2/16, or 2/17 processor
7 = PLC2/30 processor
F = computer
3 - 4 all Octal address of the start of the
PLC program.
For the 1770KF2, these bytes are
always 0.
The ladder logic starts at the end of the data table.
To find the physical end of PLC2 memory, look for FFFF
after the address in bytes 3 and 4. The FFFF must appear at
a 1/2 Kbyte junction.
5 - 6 all Memory size Size of memory (in number of bytes) for 1774PLC processor;
zero for all other processors.
7 - 8 all Diagnostic address Starting byte address of diagnostic counters and timers.