7–27Communication Commands
Publication
17706.5.16 - October 1996
set timeout
Sets the maximum amount of time that the asynchronous interface
module waits for an acknowledgment to its message transmission.
The setting is expressed as the number of cycles of an internal clock.
(For example, 40 cycles equals 1 second for the 1770-KF2.)
C
CMD
06
STS
FNC
04
TNS DATA
R
CMD
46
STS
TNS
DST SRC
SRC DST
See
the following table for settings and defaults for the module you are
setting. Put the number of desired cycles in the DA
T
A field.
DATA:
Module
Cycles/Sec Default
1770KF2 40
128 cycles (approx. 3 sec)
1771KE/KF 40
128 cycles (approx. 3 sec)
1771KG 38
38 cycles (approx. 1 sec)
1771KGM 63
63 cycles (approx. 1 sec)
1775KA 40
128 cycles (approx. 3 sec)
1785KE 29
128 cycles (approx. 4.5 sec)
set variables
Sets the maximum ENQs, NAKs, and timeout all at once.
This command is a combination of the set NAKs, set CPU mode, and
set timeout commands.
C
CMD
06
STS
FNC
02
TNS
R
CMD
46
STS
TNS
DATA
(3 bytes)
DST SRC
SRC DST
DAT
A - Put the timeout setting in the first byte, the NAKs setting in the second byte, and the
ENQs in the third byte.
• PLC2
• PLC3
• PLC5
• PLC2
• PLC3
• PLC5