1-18 Connect to the GuardPLC Controller
To recover from this fault:
1. Choose Extra>Change System ID from the Control Panel.
2. Verify that 60000 appears in the first window with 0 in the
second, as shown below.
3. Click OK.
The Fault LED should turn off, and the Control Panel should show
that the CPU State has changed to STOP/VALID CONFIGURATION, as
shown below.
TIP
The Online indicator is white because the GuardPLC
controller is in STOP/VALID mode.