Rockwell-automation 1753-PCS-PAR Using RSLogix Guard PLUS! with GuardP Manual do Utilizador Página 110

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 122
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 109
Publication 1753-PM001A-EN-P - November 2005
B-4 Configure the GuardPLC OPC Server
7. Drag G16OPC01 onto the OPC-Server Resources Editor.
The Specify HH-Network Configuration for OPC dialog opens.
8. Click OK.
Connect Signals
1. Choose the Signals pulldown menu from the menu bar and
choose Editor.
2. Add two new signals:
DI1 - input sent to the OPC Server
DO1 - output sent from the OPC Server
3. Left-click 1 in the OPC-Server Resources Editor. Choose Connect
OPC-Signals.
4. Drag DO1 from the Signal Editor to the Inputs section of the
OPC Signal Connections window.
Vista de página 109
1 2 ... 105 106 107 108 109 110 111 112 113 114 115 ... 121 122

Comentários a estes Manuais

Sem comentários