Default Data Maps D-9
1734-IJ Encoder/Counter Module
Message size: 6 Bytes
1734-IK Encoder/Counter Module
Message size: 6 Bytes
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Produces (scanner Rx) Channel 0 value of present counter state (LSW)
Channel 0 value of present counter state (MSW)
PE EF NR 0 0 0 0 0 0 ZS BS AS C1 C0 ZD 0
Where: PE = Programming error
EF = EEPROM fault status
NR = Not ready status bit
ZS = Z input status
BS = B input status
AS = A input status
C = Stored data count
ZD = Zero frequency detected
LSW = Least significant word
MSW= Most significant word
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Produces (scanner Rx) Channel 0 value of present counter state (LSW)
Channel 0 value of present counter state (MSW)
PE EF NR 0 0 0 0 0 0 ZS BS AS C1 C0 ZD 0
Where: PE = Programming error
EF = EEPROM fault status
NR = Not ready status bit
ZS = Z input status
BS = B input status
AS = A input status
C = Stored data count
ZD = Zero frequency detected
LSW = Least significant word
MSW = Most significant word