Rockwell-automation 150 USE MN/SMC DIALOG + CONTROLLER Manual do Utilizador Página 18

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 17
1-8
Product Overview
Protection and Diagnostics
(cont.)
Stall Protection and Jam Detection
The SMC Dialog Plus controller provides both stall protection and
jam detection for enhanced motor and system protection.
Stall protection is user-adjustable from 0.0 to 10.0 seconds (in
addition to the ramp time programmed).
Jam detection allows the user to determine the jam level (up to
999% of the motor’s FLC rating) and the delay time (up to 10.0
seconds) for application flexibility.
Figure 1.8 Stall Protection
Figure 1.9 Jam Detection
Jam detection is disabled during slow speed and braking operation.
Stall
600%
Percent
Full
Load
Current
Time (seconds)
Programmed Start Time
100%
Running Jam
Percent
Full
Load
Current
Time (seconds)
User Programmed Trip Level
Vista de página 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 188 189

Comentários a estes Manuais

Sem comentários