MBB October 2005
11
Triguard
SC300E MBB Bus Extender Module
SERVICING
SCOPE
The
MBB
is
not
field
repairable.
Field
servicing
operations
are
confined
to
the
total
replacement
of
faulty
MBBs.
Return
faulty
MBBs
for
repair.
DIAGNOSIS
A faulty
MBB
will
be
apparent
by
a single
I/O
channel
failure
affecting
all
the
field
devices
serviced
by
a particular
extension
chassis.
The
Health
LED
may
also
extinguish.
CONFIGURATION
There are no on
-
board
configurable
links.
Refer
to
section
Figure
2
-
5 for
chassis
address
link
settings.
REMOVAL AND REPLACEMENT
Withdraw
the
faulty
MBB
using
the
ejector
levers
and
replace
it
with
a serviceable
one
and
check
that
the
Health
LED
illuminates.
When
the
MBB
is
withdrawn
from
the
chassis
Fault
bit
1 will
be
set
immediately.
The
corresponding
MPP
may
halt,
this
will
depend
on
the
length
of
time
the
MBB
slot
remains
empty
and
on
the
progress
of
the
diagnostic
task
stepping
through
the
system
(1
second
per
slot).
If
the
MPP
does
halt
carry
out
a warm
start
after
the
serviceabl
e MBB
has
been
fitted.